Gas boiler control system

It can realize centralized monitoring of gas boilers, connect burners and gas alarms, external network circulating pump systems, make-up water pump systems, and softened water systems to achieve monitoring of all boiler operating parameters.

Boiler Energy Saving Control and Safety Interlocking
1. The system has automatic, manual and local three-zone control mode. The default is automatic operation. When needed, it can be switched to manual. By operating the computer or operating console button or local operation.
2. The control of the outlet temperature controls the opening of the outlet valve. When the temperature is high, it reduces the opening of the valve and reduces the load on the gas boiler.
3 variable flow control boiler system load, rely on the frequency conversion pump control.
4. Backwater pressure control control, depending on the frequency conversion pump control, can set the sleep frequency.
5. The safe operation of the system, alarm when the pressure is high, pressure relief in time, emergency shutdown when the high temperature is high.
6. The safe operation of the system, the alarm and adjustment of the normal water level of the drum, and the emergency shutdown control at an ultra-low level.
7. Real-time recording and archiving of the system's operating conditions.
8. Real-time recording and archiving of system alarms and abnormal conditions.